Substation O&M
Looking for Substation Operation & Maintenance in India? Check Akuntha’s Service for Substation Operation & Maintenance.
Substation Operation & Maintenance
Akuntha is leading contractor in substation operation and maintenance work.
Akuntha employs hundreds of electrical engineers on its payrol to provide guaranteed substation o&m services.
All inspection and actions during substation maintenance should be accurately documented
and stored for further reference.
Akuntha shall assume overall responsibility for operations and maintenance of the Substation.
We are a 24X7 service provider in the field of operation, maintenance, and testing of electrical equipment for power plants, transmission lines, and substations.
Our skilled manpower, latest technologies, efficient control system, modern tools, and tackles for Operation and Maintenance have established us as a deemed company in the field of Power Plant and Transmission related Substation O&M for the electrical power distribution industry.
Akuntha Projects Private Limited is proud to be the participant company in Gujarat Electricity Generation, Transmission, and Distribution ecosystem and we provide Erection, Operations, and Maintenance services – O&M of 66 kV electric substations. Though our major client is government-owned agencies, we also provide substation O&M services to private companies.
Routine Substation Operation & Maintenance Activities
Daily activities and routine inspection carried out.
Monitoring reading continuously and keeping records.
All kind of periodic testing of
switchyard equipment.
All kind of testing for control room panel equipment/relays.
Resetting of machine in case of abnormal tripping/after clearing faults.
Constant monitoring of power transmission.
Experienced staff and security are on duty 24/7 to respond quickly to any situation in the substations.
Training for each and every individual in line with new developments in power technology.
Resetting of machine in case of abnormal tripping/after clearing faults.
Liaison with GETCO for HV/EHV line clearance & grid failure.
Replacement of spares only if repairing fails.
Liaison with GETCO for HV/EHV line clearance & grid failure.
Checking of feeder & main line by thermal imager to point out weak links and remedial action thereafter to avoid any line fault during operation.
Tie up with different agencies involved in transmission of electrical power industry to meet any kind of challenge faced and reduce response time drastically.
Preventive Maintenance
Key Elements of Substation O&M
Visual Inspection
Current transformers are normally filled with oil and have oil impregnated paper insulation for both primary and secondary winding. Careful inspection is to be made for any trace of oil leakages. Oil leakages are more prone through cemented joints or secondary terminal box due to improper sealing of terminal studs.
Visual inspection is also to be carried out on the healthiness of terminal connections, condition of porcelain, development of cracks, chippings, cleanliness of insulator surface, etc.
Maintenance of Gaskets
Marshaling boxes and CT terminal boxes must be sealed properly to ensure that any dust, rainwater, or insects are not able to enter the compartment. It is essential that door gaskets be replaced periodically to maintain a high level of sealing efficiency.
Furthermore, it is vitally important that all door bolts and latches are securely tightened and never left in a state of looseness. Doing so will ensure the highest level of security at all times, while also preserving the integrity of the door itself.
Secondary Terminal Connections
Stud type terminals are preferred in Marshalling box cable terminals. This gives better grip even if more than one wire is connected to one terminal. But pin type terminals are also provided in some cases. Since tightness of wires may become loose due to vibration, climatic condition, it is required to check tightness of terminals periodically to avoid maloperation / non-operation due to improper contacts.
All terminals of unused CT secondary terminals are to be properly shorted to avoid development of abnormal voltage and subsequent failure of CTs. The tan δ test tap is to be properly earthed to avoid damage to insulation
Primary Terminals
Thermovision scanning can help to quickly and accurately indicate proper connection of the primary terminal. If thermovision is not carried out, a more thorough approach of physical checking of terminal connections should be conducted with the appropriate torque specifications followed.
Furthermore, all required corona shields should be carefully installed to provide maximum protection from electrical disturbances.
Any malfunctioning or damaged corona shields should be immediately replaced with new ones to guarantee the best possible performance.
How does a 33, 66, 132 or 220 kV Substation Work?
A substation is a crucial component of an electrical power system, facilitating the transmission and distribution of electricity. It converts high-voltage power from generators to lower voltage levels suitable for distribution. Step-up transformers increase the voltage for long-distance transmission, while step-down transformers lower it for distribution.
Transmission lines equipped with protective devices deliver the high-voltage electricity to the substation. Inside the substation, switchgear and distribution equipment control and direct the flow of electricity. The stepped-down electricity is then distributed through a network of lines to end consumers. Overall, the substation ensures efficient and safe power transmission and distribution.
Capacitance Voltage Transformers, Potential
Transformers, Capacitor Coupling
Visual Inspection
The most of the CVTs are not visible from outside. CTs/CVTs and CC are also oil filled equipment’s and . If oil leak is observed in anyone stack, the entire CVT is to be replaced. CVTs are tuned units and replacement of anyone stack is not recommended to phase angle errors.
Electro-Magnetic Unit
Electro-Magnetic Unit (EMU) of CVT houses the secondary transformer, Compensating reactor and . The colour of oil indicated through the gauge: glass gives some indication of the healthiness of the internal components.
Secondary Voltage
Deviation in secondary Voltage of CVT is . Necessary action to be taken to replace CVT if secondary voltage in anyone CVT is abnormal (may be +2V and -4V). Continuing the equipment in service beyond this stage may lead to failure/bursting of CVTs.
Other Maintenance
Maintenance of marshalling box gaskets, tightening of secondary terminal connections and tightening of primary terminal connections, etc., are also to be ensured for healthy operation. It is to be ensured that all extra holes at Marshalling boxes are properly plugged and kept vermin proof.
Let's make our world a better place by developing and providing access to sustainable and dependable energy sources.
2000
Projects Completed
In the last 8 years
90
Happy Customers
Who Trusted Us
Leading Substation Operation & Maintenance Contractor Company in India
Akuntha Projects Private Limited is a dominant company in the Gujarat Electricity Distribution ecosystem and we provide Erection, Operations, and Maintenance services (O&M) of 33kV, 66 kV, 132 kV and higher electric substations. With huge experience in maintaining dozens of substations, we employ a large number of electric engineers on our payroll.
Technical Expertise
We utilise cutting-edge equipment and advanced technology to optimise substation operation and maintenance. Our latest tools ensure precise diagnostics, efficient maintenance procedures, and reliable performance. By harnessing automation, monitoring systems, and innovative solutions, we deliver exceptional results, enhancing efficiency of your substations.
Safety-Driven Operations
Our team specialise in substation operation and maintenance, ensuring reliable and efficient power systems. With a background in electrical engineering and extensive training, we handle all aspects of maintenance, including testing, preventive measures, and fault management.
Safety is our priority, as we adhere to industry regulations and implement proactive procedures. Our expertise extends to control systems, emergency response, and environmental maintenance. Trust Akuntha to optimize substation performance, ensuring uninterrupted power supply for your operations.
We Install And
Service Projects
We specialize in installing and servicing projects of all sizes, from small residential projects to large-scale commercial installations. Our team of highly experienced professionals are committed to providing top-notch service with the utmost care and attention to detail. We utilize the latest technologies to make sure that your project is properly installed, serviced, and maintained with optimal efficiency. Our goal is to deliver quality results on time and within budget while consistently exceeding your expectations.
Akuntha Ground Mount Solar Solutions Include:
Akuntha Projects Private Limited is one of the leading turnkey EPC services providers in the Indian solar industry. For ground-mount solar solution, we have the state of the art services which ensure a higher return on investment by reducing your electricity bills. Our customized solutions have helped various industrial and commercial customers by adopting sustainable solar solutions thus reducing their carbon footprint.
Building Integrated Systems
Rooftop Solar
Parking Structures
Ground Mount
Solutions
Solar Power Feasibility For Your Business or Public Agency Building
We have designed these solar grid-tie systems for business.
We apply years of experience to our custom system details for the commercial property owner, industrial facility manager, solar farm, or homeowner with a business on their property. Good common sense dictates that economic feasibility be a factor in your solar power business. decision.
Grid-tie solar electric systems for commercial businesses are the fastest-growing segment of the solar market worldwide. With net metering programs now approved in most areas, thousands of businesses, and schools are now experiencing the benefits of solar electricity.
Why should I buy a ground-mounted solar system
from Akuntha?
Through our purchasing volume, Akuntha has negotiated the best pricing on solar modules, inverters, and the balance of system equipment.
We provide a complete custom-designed integrated solar power system for your facility at the lowest possible price. We encourage you to get an installed price for a solar power system and then compare it to our system prices.
Frequently Asked Questions
Substation operation ensures reliable electricity distribution, voltage control, and system protection.
Proper maintenance reduces energy losses and extends the lifespan of equipment, promoting sustainability.
Maintenance includes inspection, testing, cleaning, and repair of substation equipment.
Regular inspections help identify issues early and prevent potential failures.
afety measures like lockout/tagout, personal protective equipment, and training are crucial for substation maintenance.